Home About Us Contact Us Product Range Search WSX News         
      Pyroplex ATG Fire Grille
          Tel: +44 (0)1329 221111    UK Freefax: 0800 731 4683    Int. Fax: +44 (0)1329 221122    Email: sales@wis-ltd.com

Acoustic Seals
Conservatory Glazing
Draught & Weather
Finger Protection
Fire Protection
Joinery & Glazing

DESCRIPTION

Manufactured from high performance intumescent material that is formed into square or rectangular shapes and contained within a steel frame, for use in fire resisting door sets and compartment walls to provide up to 60 minutes fire resistance. 

In normal use the grilles allow air to be circulated and moved throughout the building; however on exposure to heat from a fire the intumescent material swells to produce a fire resistant seal against the passage of fire, smoke and hot gases. The grilles are easily installed in vertical apertures in doors or walls.  We can also supply a range of square or rectangular steel louvered faceplates in a painted silver aluminium finish to provide an aesthetically pleasing finish. (Other finishes available to order). 

The product has been independently tested by Bodycote/Warrintonfire to BS476 part 22:1987 for 30 and 60 minute fire resistance. Test Reports 146520/146521 & 148053 apply – combined within Assessment Report No. 149511. The product has Certifire CF549 accreditation.

 

AVAILABILITY

Product Ref

ATG1500

ATG2251

ATG2250

ATG1503

ATG1300

Size  W x H x T mm

150 x 150 x 40

225 x 112 x 40

225 x 225 x 40

300 x 150 x 40

300 x 300 x 40

Free Air Flow cm2

152

161

323

304

614

 

Face Plates Ref

FP150150

FP250100

FP250250

FP300150

FP300300

Louvred Area mm

150 x 150

250 x 100

250 x 250

300 x 150

300 x 300

Overall Size mm

193 x 193

295 x 143

295 x 295

346 x 193

346 x 346

 
   

INSTALLATION

Cut an aperture in the door and line with a 6mm-hardwood liner. Apply a bead of intumescent mastic centrally around and spread across the full width of the liner to achieve a thickness of 0.5mm. Install the ATG into the aperture and secure in place using steel pins or self-tapping screws. Finally fit the face plates to both sides and secure with screws provided.

In all cases the installer must ensure that the doorset/door blank has been tested with an aperture to accept an intumescent ATG for the required period of fire resistance. Failure to comply with the requirements and instructions detailed in the specification of the doorset/blank may invalidate the fire resistance period of the fire resisting door assembly. In fire door assemblies the fire grilles must be installed no closer than 150mm to the threshold and no higher than 1850mm.

 

HEALTH AND SAFETY

The product does not present any known health hazards during or after installation.

Normal good industrial and personal hygiene practises should be observed.

For detailed information on this product please request relevant MSDS.

 

Important - not suitable for use in air conditioning systems - refer to  Firecheck Dampers

 


Copyright © 2007, 2010 Wessex Intumescent Supplies Ltd.

Use of Data, Legal and Privacy Policy

Pyro-Seal is a registered trademark of Wessex Intumescent Supplies Ltd.

All goods sold or offered are subject to our terms and conditions of sale.